Statistical approach for determining impulse breakdown voltage distribution under DC sweep voltage

1Citations
Citations of this article
6Readers
Mendeley users who have this article in their library.

Abstract

This paper presents a comprehensive approach to the statistical characterization of impulse breakdown voltage under the effect of a DC sweep voltage. Several goodness-of-fit tests are applied to up-and-down test results obtained in the air-insulated rod-plane gap. Three distributions, normal, logistic, and Gumbel, are compared by means of the Kolmogorov-Smirnov goodness-of-fit test, and logistic distribution is also compared to 3-parameter Weibull distributions using the likelihood ratio test. Logistic distribution is found to be a possible alternative to normal and 3-parameter Weibull distributions. © TÜBİTAK.

Cite

CITATION STYLE

APA

Demir, M., & Koraşli, C. (2014). Statistical approach for determining impulse breakdown voltage distribution under DC sweep voltage. Turkish Journal of Electrical Engineering and Computer Sciences, 22(1), 12–24. https://doi.org/10.3906/elk-1206-56