Domestic drinking water supply systems (DDWSs) are the final step in the delivery of drinking water to consumers. Temperature is one of the rate-controlling parameters for many chemical and microbiological processes and is, therefore, considered as a surrogate parameter for water quality processes. In this study, a mathematical model is presented that predicts temperature dynamics of the drinking water in DDWSs. A full-scale DDWS resembling a conventional system was built and run according to one year of stochastic demands with a time step of 10 s. The drinking water temperature was measured at each point-of-use in the systems and the data-set was used for model validation. The temperature model adequately reproduced the temperature profiles, both in cold and hot water lines, in the full-scale DDWS. The model showed that inlet water temperature and ambient temperature have a large effect on the water temperature in the DDWSs.
CITATION STYLE
Zlatanovic, L., Moerman, A., van der Hoek, J. P., Vreeburg, J., & Blokker, M. (2017). Development and validation of a drinking water temperature model in domestic drinking water supply systems. Urban Water Journal, 14(10), 1031–1037. https://doi.org/10.1080/1573062X.2017.1325501