Detection of dissolved carbon monoxide in transformer oil using 1.567 m diode laser-based photoacoustic spectroscopy

16Citations
Citations of this article
8Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

Carbon monoxide (CO) is one of the most important fault characteristic gases dissolved in power transformer oil. With the advantages of high sensitivity and accuracy, long-term stability, and short detection time, photoacoustic spectroscopy (PAS) has been proven to be one promising sensing technology for trace gas recognition. In this investigation, a tunable PAS experimental system based on a distributed-feedback (DFB) diode laser was proposed for recognizing dissolved CO in transformer oil. The molecular spectral line of CO gas detection was selected at 1.567 m in the whole experiment. Relationships between the photoacoustic (PA) signal and gas pressure, temperature, laser power, and CO gas concentration were measured and discussed in detail, respectively. Finally, based on the least square regression theory, a novel quantitative identification method for CO gas detection with the PAS experimental system was proposed. And a comparative research about the gas detection performances performed by the PAS system and gas chromatography (GC) measurement was presented. All results lay a solid foundation for exploring a portable and tunable CO gas PAS detection device for practical application in future.

Cite

CITATION STYLE

APA

Zhou, Q., Tang, C., Zhu, S., Chen, W., & Peng, X. (2015). Detection of dissolved carbon monoxide in transformer oil using 1.567 m diode laser-based photoacoustic spectroscopy. Journal of Spectroscopy, 2015. https://doi.org/10.1155/2015/737635

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free