Investigation into the lithium-ion battery fire resistance testing procedure for commercial use

7Citations
Citations of this article
23Readers
Mendeley users who have this article in their library.

Abstract

Lithium-ion batteries (LIBs) have many advantages (e.g., high voltage and long-life cycle) in comparison to other energy storage technologies (e.g., lead acid), resulting in their applicability in a wide variety of structures. Simultaneously, the thermal stability of LIBs is relatively poor and can be damaged by exposure to fire. This paper presents an investigation into a fire resistance safety test for LIBs and the use of thermal sensors to evaluate exposure conditions and estimate the temperatures to which cells are subjected. Temperature distribution data and statistical analysis show significant differences of over 200◦C, indicating the stochastic nature of the heating curve despite following the testing procedure requirements. We concluded that the current testing procedure is inadequate for the reliable testing of LIBs, leaving an alarming loophole in the fire safety evaluation. The observed instability is mostly related to wind speed and direction, and fire source size.

Cite

CITATION STYLE

APA

Darnikowski, D., & Mieloszyk, M. (2021). Investigation into the lithium-ion battery fire resistance testing procedure for commercial use. Batteries, 7(3). https://doi.org/10.3390/batteries7030044