Normal operation and reverse action of on-load tap changing transformer with its effect on voltage stability

6Citations
Citations of this article
16Readers
Mendeley users who have this article in their library.

Abstract

As electrical grids have expanded significantly, so too has the load on network buses. This, however, causes voltage drops to occur at the load side of the grid. A voltage drop causes a system to become unstable, increases its power loss, and reduces the amount of power that it transfers before finally leading to a collapse. An on-load tap changing (OLTC) transformer can be used to prevent the negative effects of an increased load by restoring the load voltage to its base value when sudden disturbances occur in the source. However, incorrect OLTC placement can cause the system to become unstable and cause collapse. This is referred to as the reverse action phenomenon of an OLTC. Therefore, this present study examined improving the ability of an OLTC to increase system stability and prevent collapse. A simple radial power distribution system was modelled in MATLAB. The results indicate that the proposed model can increase system stability and prevent collapse.

Cite

CITATION STYLE

APA

Alkahdely, S. M. A., & Alsammak, A. N. B. (2023). Normal operation and reverse action of on-load tap changing transformer with its effect on voltage stability. Bulletin of Electrical Engineering and Informatics, 12(2), 650–658. https://doi.org/10.11591/eei.v12i2.4556