The paper presents the results of the UFAD system numerical modeling where the air is supplied through diffusers installed in a floor of a room. Warm air is removed from the upper zone of the room through the exhaust duct. The purpose of this study is to determine the magnitude of the temperature stratification in various areas of an office premise in the conditions of the under floor air distribution. Enclosed volume with local heat sources has been chosen as the computational domain: people, computers, and lighting. The problem is solved in a stationary setting using the k-omega SST turbulence model. As a result of the study the temperature distribution throughout the room has been obtained and the influence dependence of wall temperature on an average air temperature in the room has been defined. The numerical data received are in good agreement with the results of the borrowed experimental study that demonstrate the adequacy of the developed numerical model as well as the possibility of its further use for the optimization of the considered ventilation systems.
CITATION STYLE
Nikitin, M., Tsynaeva, A., & Mazynskaya, S. (2017). The stratification study of public buildings microclimate parameters with supply and exhaust ventilation. In MATEC Web of Conferences (Vol. 106). EDP Sciences. https://doi.org/10.1051/matecconf/201710606018