In recent years, the demand for high-reliability systems has been on the rise, while DC power distribution systems are widely used in data centers. The authors propose a DC power distribution system that uses a triple active bridge (TAB) DC-DC converter, toward the realization of such higher-reliability systems. The TAB converter is based on an isolated DC-DC converter and can control the DC power flow among the three ports. First, this paper presents a basic power flow control procedure of the TAB converter, using a phase-shift control. Further, two types of higher-reliability DC power distribution systems are proposed using the TAB converter. The experimental design and simulations of a prototype 200-V TAB converter with 500-W power, connected with the single and double loads, are reported. In the experiment, the 200-V TAB converter rated at a power of 500 W was constructed from a three-winding transformer and gallium nitride (GaN) power devices. Smooth output waveforms indicate good controllability of the power flow and good functional performance of the proposed DC power distribution system.
CITATION STYLE
Yu, Y., Wada, K., Masumoto, K., & Kado, Y. (2018). A DC power distribution system In a data center using a triple active bridge DC-DC converter. IEEJ Journal of Industry Applications, 7(3), 202–209. https://doi.org/10.1541/ieejjia.7.202