Power stability analysis and evaluation criteria of dual-infeed HVDC with LCC-HVDC and VSC-HVDC

6Citations
Citations of this article
6Readers
Mendeley users who have this article in their library.

Abstract

This paper analyzes the power stability of the hybrid dual-infeed high-voltage direct-cur-rent (HVDC) system containing a line commutated converter-based HVDC (LCC-HVDC) and a voltage source converter-based HVDC (VSC-HVDC). First, the concept and the calculation method of power stability for the hybrid dual-infeed HVDC system are introduced. Second, the influence of VSC-HVDC on the power stability of the system is investigated. Third, the relationship between the power stability and the effective short circuit ratio (ESCR) is discussed under different system pa-rameters. Then, the value range of the critical effective short circuit ratio is determined. Finally, the evaluation criteria of power stability are proposed. The results show that the evaluation criteria of the single-infeed LCC-HVDC system can still be used, if the VSC-HVDC is in constant AC voltage control mode; if the VSC-HVDC is in constant reactive power control mode, the hybrid dual-infeed HVDC system cannot operate stably when the ESCR is less than 2.0 and can operate stably with high power stability margin when the ESCR is greater than 3.0. The ESCR index can still be used to measure the power stability of the hybrid dual-infeed HVDC system.

Cite

CITATION STYLE

APA

Wu, X., Xu, Z., & Zhang, Z. (2021). Power stability analysis and evaluation criteria of dual-infeed HVDC with LCC-HVDC and VSC-HVDC. Applied Sciences (Switzerland), 11(13). https://doi.org/10.3390/app11135847

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free