High Impedance Fault Line Detection Based on Current Traveling Wave Spectrum Symmetry Driving for New Distribution Network

3Citations
Citations of this article
11Readers
Mendeley users who have this article in their library.

Abstract

Challenges are brought to high impedance fault (HIF) line selection in traditional distribution networks by the fault signals with short windows and weak characteristics provided by new energy power sources. A new method driven by the symmetry of current traveling wave spectrum is proposed in this paper. Frequency-domain features are extracted by using Pisarenko spectral decomposition, and the differences in amplitude, frequency, and polarity between faulted and healthy feeders are analyzed. A similarity matrix is constructed with the help of Manhattan distance, and an improved density-based spatial clustering of application with noise (DBSCAN) clustering is adopted to achieve intelligent fault line selection. Experimental results show that compared with the steady state component method and the transient component method, the accuracy of this method is increased to 97.5%, with an improvement of more than 12.5%. Quantitative thresholds are replaced by qualitative spectrum differences, and this method is not affected by weak signals, thus solving the problem of threshold setting caused by the access of new energy. The accuracy of this method under different fault types, phases, and resistances is verified by simulation, ensuring easy engineering implementation.

Cite

CITATION STYLE

APA

Xiao, M., Zeng, J., Zhou, Z., Zhang, Q., Deng, L., & Peng, F. (2025). High Impedance Fault Line Detection Based on Current Traveling Wave Spectrum Symmetry Driving for New Distribution Network. Symmetry, 17(5). https://doi.org/10.3390/sym17050775

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free