Calculation of distance protection settings in mutually coupled transmission lines: A comparative analysis

15Citations
Citations of this article
31Readers
Mendeley users who have this article in their library.

Abstract

Protection of mutually coupled transmission lines poses special challenges to protection engineers, since the general principles outlining the expected performance of the protection elements are based on simplified versions of the issues affecting them. Distance protection elements are among the most commonly accepted methods for protecting mutually coupled transmission lines, however, the calculation of settings and the validation of their performance is a complex task, involving lots of simulations and analysis of results to come up with an acceptable solution. Though various methods have been proposed to deal with the problem of calculating the optimal settings of distance protection elements, there is still room for improvement, since these methods have been formulated for the general case considering simple transmission lines. In this paper, a variation of one of these methods is introduced to enhance the computing times and reliability of the solutions for the specific application of quadrilateral distance protection to mutually coupled transmission lines, through the characterization of the expected performance of the operating characteristic, and the formulation of the optimization problem and the solution method. The obtained results show the improvements in computing times and quality of the solution provided by the proposed algorithm.

Cite

CITATION STYLE

APA

de Jesús Jaramillo Serna, J., & López-Lezama, J. M. (2019). Calculation of distance protection settings in mutually coupled transmission lines: A comparative analysis. Energies, 12(7). https://doi.org/10.3390/en12071290

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free