Theoretical study of low-GWP refrigerants in high-temperature heat pump systems

6Citations
Citations of this article
15Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

In this paper, the thermal performance of three low-global warming potential refrigerants R1224yd(Z), R1223zd(E) and R1336mzz(Z) were studied to replace R245fa in the high-temperature heat pump system. The results showed that the heating capacity of R1224yd(Z), R1223zd(E) and R1336mzz(Z) was 6, 12 and 88% less than that of R245fa, respectively. The coefficient of performance (COP) of R1224yd(Z) and R1223zd(E) was 2 and 1% higher than that of R245fa, respectively. However, the COP of R1336mzz(Z) was 5% less than that of R245fa. The difference in compressor discharge temperature between R1224yd(Z), R1223zd (E), R1336mzz(Z) and R245fa was about ±5◦C. R1224yd(Z) is the best refrigerant to replace R245fa. R1223zd(E) is the second. R1336mzz(Z) cannot be directly replaced unless the original system is modified.

Cite

CITATION STYLE

APA

Zhou, D., Meng, Z., Liu, Y., Dong, S., Zhang, F., Ding, C., … Wang, M. (2023). Theoretical study of low-GWP refrigerants in high-temperature heat pump systems. International Journal of Low-Carbon Technologies, 18, 881–886. https://doi.org/10.1093/ijlct/ctad059