SF 6 Byproducts in High-Humidity Environment: an Experimental Evaluation between 200 o C and 500 o C

  • Wang Y
  • Li L
  • Yao W
N/ACitations
Citations of this article
7Readers
Mendeley users who have this article in their library.

Abstract

Abstract: In the occurrence of arc discharges, spark discharges, corona discharges and overheated faults in electrical equipment, SF 6would be decomposed to complicated byproducts, such as SO2 , H2S and HF. Analyzing these byproducts is an effective method to judge the internal operation condition of electric equipment. In order to study characters of SF6byproducts at different temperature of overheated faults in the electric equipment, a series of overheated faults of electric equipment were simulated. SF6is very stable and not significantly decomposed at 200oC, 250oC and 300oC. SF6is significantly decomposed to SO2, H2S and HF at 350oC. The concentration of SO2, H2S and HF was 7.2, 1.6 and 1.9 μL/L after heating for 5 hours in environment of SF6with 3616 μL/L water, and it was increased to 23.0, 3.0 and 1.2 μL/L 3 hours later. SF6is more easily to be decomposed and decomposed more rapidly at higher temperature. The concentration of SO2, H2S and HF was 62.2, 15.6 and 3.6 μL/L after heating for 5 hours in environment of SF6with 4064 μL/L water, and it was increased to 91.4, 25.2 and 2.3 μL/L 3 hours later. SF6will be decomposed to format HF, which is strongly corrosive and whose concentration is likely to decrease when it is above a certain concentration.

Cite

CITATION STYLE

APA

Wang, Y., Li, L., & Yao, W. (2011). SF 6 Byproducts in High-Humidity Environment: an Experimental Evaluation between 200 o C and 500 o C. Journal of Electromagnetic Analysis and Applications, 03(06), 179–183. https://doi.org/10.4236/jemaa.2011.36029

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free