Estimation of conservation voltage reduction factors using measurement data of KEPCO system

8Citations
Citations of this article
9Readers
Mendeley users who have this article in their library.

Abstract

This paper describes a method to estimate conservation voltage reduction (CVR) factors using data measured in power distribution systems. A direct method is proposed to estimate CVR factors using only data measured at the moment of the transformer tap change. The mean absolute deviation (MAD) direct method is proposed to consider direct methods and load variations. The proposed methods do not necessitate intentional tap changes for testing purposes. Instead, the voltage and load changes that occur when the tap changes, for voltage regulation purposes, are measured and utilized in the CVR factor calculation. The proposed methods were tested using data obtained from the Korea Electric Power Corporation (KEPCO) system, and the results revealed that CVR factors for both active power and reactive power could be estimated using data measured in power distribution systems. Results of the CVR factor estimation for the active power revealed that the highest CVR factors occurred in winter, during which a large quantity of heating loads exist. In addition, the estimated CVR factors for the reactive power were higher than the estimated CVR factors for the active power because reactive power is more sensitive to voltage changes.

Cite

CITATION STYLE

APA

Shim, K. S., Go, S. I., Yun, S. Y., Choi, J. H., Nam-Koong, W., Shin, C. H., & Ahn, S. J. (2017). Estimation of conservation voltage reduction factors using measurement data of KEPCO system. Energies, 10(12). https://doi.org/10.3390/en10122148

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free