Study of Hybrid Transmission HVAC/HVDC by Particle Swarm Optimization (PSO)

4Citations
Citations of this article
14Readers
Mendeley users who have this article in their library.

Abstract

There are considerable power losses in Indonesia’s SUMBAGUT 150 kV transmission High Voltage Alternating Current Network (HVAC) system. These power losses and the voltage profile are critical problems in the transmission network system. This research provides one possible way to reduce power losses involving the use of a High Voltage Direct Current (HVDC) network system. Determining the location to convert HVAC into HVDC is very important. The authors of the current study used Particle Swarm Optimization (PSO) to determine the optimal location on the 150 kV SUMBAGUT HVAC transmission network system. The study results show that, before using the HVDC network system, the power loss was 68.41 MW. On the other hand, power loss with the conversion of one transmission line to HVDC was 57.31 MW for “Paya Pasir–Paya Geli” (efficiency 16.22%), 51.79 MW for “Paya Pasir–Sei Rotan” (efficiency 24.29%), and 60.8 MW for “Renun–Sisikalang” (efficiency 110.12%). The power loss with the conversion of two transmission lines to HVDC was 45.7 MW for “Paya Pasir–Paya Geli” and “Paya Pasir–Sei Rotan” (efficiency 33.19%), 44.95 MW for “Paya Pasir–Paya Geli” and “Renun–Sidikalang” (efficiency 26.98%), and 44.69 MW for “Paya Pasir–Sei Rotan” and “Renun–Sidikalang” (efficiency 34.67%). The power loss with the conversion of three transmission lines to HVDC was 38.71 MW for “Paya Pasir–Paya Geli,” “Paya Pasir–Sei Rotan,” and “Renun–Sidikalang” (efficiency 41.41%).

Cite

CITATION STYLE

APA

Siregar, Y., & Pardede, C. (2022). Study of Hybrid Transmission HVAC/HVDC by Particle Swarm Optimization (PSO). Energies, 15(20). https://doi.org/10.3390/en15207638

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free