Study on a waste heat-driven adsorption cooling cum desalination cycle

177Citations
Citations of this article
138Readers
Mendeley users who have this article in their library.
Get full text

Abstract

This article presents the performance analysis of a waste heat-driven adsorption cycle. With the implementation of adsorption-desorption phenomena, the cycle simultaneously produces cooling energy and high-grade potable water. A mathematical model is developed using isotherm characteristics of the adsorbent/adsorbate pair (silica gel and water), energy and mass balances for the each component of the cycle. The cycle is analyzed using key performance parameters namely (i) specific cooling power (SCP), (ii) specific daily water production (SDWP), (iii) the coefficient of performance (COP) and (iv) the overall conversion ratio (OCR). The numerical results of the adsorption cycle are validated using experimental data. The parametric analysis using different hot and chilled water temperatures are reported. At 85°C hot water inlet temperature, the cycle generates 3.6 m 3 of potable water and 23 Rton of cooling at the produced chilled water temperature of 10°C. © 2012 Elsevier Ltd and IIR. All rights reserved.

Cite

CITATION STYLE

APA

Ng, K. C., Thu, K., Saha, B. B., & Chakraborty, A. (2012). Study on a waste heat-driven adsorption cooling cum desalination cycle. International Journal of Refrigeration, 35(3), 685–693. https://doi.org/10.1016/j.ijrefrig.2011.01.008

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free