Aiming at the problem of abnormal data generated by a power transformer on-line monitoring system due to the influences of transformer operation state change, external environmental interference, communication interruption, and other factors, a method of anomaly recognition and differentiation for monitoring data was proposed. Firstly, the empirical wavelet transform (EWT) and the autoregressive integrated moving average (ARIMA) model were used for time series modelling of monitoring data to obtain the residual sequence reflecting the anomaly monitoring data value, and then the isolation forest algorithm was used to identify the abnormal information, and the monitoring sequence was segmented according to the recognition results. Secondly, the segmented sequence was symbolised by the improved multi-dimensional SAX vector representation method, and the assessment of the anomaly pattern was made by calculating the similarity score of the adjacent symbol vectors, and the monitoring sequence correlation was further used to verify the assessment. Finally, the case study result shows that the proposed method can reliably recognise abnormal data and accurately distinguish between invalid and valid anomaly patterns.
CITATION STYLE
Zhao, J., Gao, S., Liu, Y., Wang, Q., Xu, Z., Tian, Y., & Sun, L. (2022). Anomaly Detection and Pattern Differentiation in Monitoring Data from Power Transformers. Energy Engineering: Journal of the Association of Energy Engineering, 119(5), 1811–1828. https://doi.org/10.32604/ee.2022.020490