Classification of common discharges in outdoor insulation using acoustic signals and artificial neural network

58Citations
Citations of this article
45Readers
Mendeley users who have this article in their library.
Get full text

Abstract

Condition monitoring of outdoor insulation systems is crucial to the integrity of distribution and transmission overhead lines and substations. The objective of this study is to use a commercial acoustic sensor along with artificial neural network (ANN), to classify different typical types of discharges in outdoor insulation systems. First, ANN was used to distinguish between five common electrical discharges that were generated under controlled conditions. Next, this approach was extended to include outdoor ceramic insulators. Three types of defects were tested under laboratory conditions, i.e. a crack in the ceramic disc, surface pollution discharge, and corona near the insulator surface. Both a single disc, and three discs connected in an insulator string were tested with respect to these defects. For both controlled samples and full insulators, a recognition rate of more than 85% was achieved.

Cite

CITATION STYLE

APA

Polisetty, S., El-Hag, A., & Jayram, S. (2019). Classification of common discharges in outdoor insulation using acoustic signals and artificial neural network. High Voltage, 4(4), 333–338. https://doi.org/10.1049/hve.2019.0113