Due to the rapid economic development in recent years, water-chiller is being used more and more in hotels, restaurants, resorts, and industrial zones in Vietnam. The cooling tower’s cooling water quality is an important factor in determining the effect on electrical consumption and the coefficient of performance of a water-cooled chiller. Therefore, it is necessary to maintain the quality of cooling water during the operation time of the water-cooled chiller. The aim of this work is to investigate the effects of the pulse frequency and operational parameters such as current density, pulse duty cycle, and energy consumption on the performance of removing hardness ion of electrochemical cooling water treatment for the cooling tower of the water-cooled chiller. The results show that the highest efficiency of the total hardness removal corresponding to a pulse frequency of 1 kHz, a pulse duty cycle of 0.7, and a current density of 80A/m2.