In this paper, heat transfer analysis for an air-air heat exchanger was experimentally carried out to find its thermal performance and effectiveness. Air-air heat exchanger equipped with finned heat pipes was considered for the experimentation. Mass flow rate of air was considered in between 0.24 to 0.53 kg/s. The temperature at the condenser side of the heat pipe heat exchanger was kept constant at around 23 °C and at the evaporator part it was varied from 88 to 147 °C. The performance of heat pipe heat exchanger was evaluated at different mass flow rate of air, in terms of effectiveness and compared with its corresponding value found by theoretical analysis.
CITATION STYLE
Mandapati, M. J. K., Subhash Chandra, K., & Sat Narayan, G. (2014). Thermodynamic performance evaluation of an AIR-AIR heat pipe heat exchanger. Thermal Science, 18(4), 1343–1353. https://doi.org/10.2298/TSCI121214123K