Multi-nozzle Closed Loop Spray Cooling Systems in Electronics Cooling

5Citations
Citations of this article
8Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

This study presents two refrigerant closed loop spray cooling systems for two specific electronic cooling applications. A small system using a 3 2 nozzle array is developed to investigate the spray cooling performance on a concentrated heat source (2 1 cm2) with a high heat flux. A big system uses a 9 6 nozzle array to cool a 6U card area (23.3 16 cm2) with a moderate uniform heat flux. The experimented flow rate in the small system is maintained at 7.8∼8.1 g/s corresponding to a spray mass flux of 3.9∼4.05 g/cm2⋅s on the concentrated heat source, and the studied flow rates in the big system are monitored at 113 4 g/s corresponding to a spray mass flux of 0.30 g/cm2⋅s on the 6U card surface area. The results show that the small system with a much higher spray mass flux can perform a spray cooling curve with a wide heat flux range. The big system with much less spray mass flux has performed a slightly better heat transfer coefficient due to its much better evaporation efficiency at the same degree of surface superheat.

Cite

CITATION STYLE

APA

Xie, J., Lee, H. M., & Xiang, J. (2018). Multi-nozzle Closed Loop Spray Cooling Systems in Electronics Cooling. In IOP Conference Series: Earth and Environmental Science (Vol. 189). Institute of Physics Publishing. https://doi.org/10.1088/1755-1315/189/2/022062