LEPIR2 testing facility is aimed to evaluate the fire behaviour of construction solutions implemented on facade according with the experimental evaluation required by the French Technical Specification 249 (IT249) of the safety regulation. It aims to limit the risks of fire spreading by facades to upper levels. This facility involves a wood crib fire in the lower compartment of a full scale two levels high structure. Flames are coming outside from the compartment through windows openings and develop in front of the facade. Computational fluids dynamics simulations are carried out with the FDS code (Fire Dynamics Simulator) for two full-scale experiments performed by Efectis France laboratory. The first objective of this study is to evaluate the ability of numerical model to reproduce quantitative results in terms of gas temperatures and heat flux on the tested facade for further evaluation of fire performances of an insulation solution. When experimental results are compared with numerical calculations, good agreement is found out for every quantities and each test. The proposed models for wood cribs and geometry give correct thermal loads and flames shape near the tested facade.
CITATION STYLE
Dréan, V., Schillinger, R., & Auguin, G. (2016). Fire exposed facades: Numerical modelling of the LEPIR2 testing facility. In MATEC Web of Conferences (Vol. 46). EDP Sciences. https://doi.org/10.1051/matecconf/20164603001