Mutual coupling compensation techniques used for distance protection of parallel lines

8Citations
Citations of this article
11Readers
Mendeley users who have this article in their library.

Abstract

When a distance relay protects a transmission line located on a dual circuit tower, a coupling effect will occur between the two circuits. Transposition of the circuits can reduce the mutual impedances, but this does not cater to the zero-sequence mutual coupling impedance during earth faults. As a result, the impedance measured by a distance relay under phase-to-earth fault conditions in these circumstances will not represent the correct impedance to the fault point unless these effects are taken into account. On multi-circuit lines, primarily if they operate in parallel, a zero-sequence mutual coupling should be considered when calculating settings for distance protection function. A 220 kV parallel line sharing the same tower was analysed using DigSilent Power Factory in the simulations. Phase-to-earth faults in different configurations were analysed on this system, and the reach of the protection relay was then estimated for operation. The results confirm how a protection relay can overreach and underreach in a distance protection scheme due to the influence of mutual coupling.

Cite

CITATION STYLE

APA

Donovan, M. O., Barry, N., Connell, J., & Cowhey, E. (2021). Mutual coupling compensation techniques used for distance protection of parallel lines. Energies, 14(7). https://doi.org/10.3390/en14071982