Transient stability of doubly-fed induction generators (DFIGs) is a major concern in both AC and DC grids, and DFIGs must stay connected for a time during grid faults according to the power grid requirements. For this purpose, this work proposes an overcurrent and overvoltage protective device (OCV-PD) to ensure that DC-based DFIG system can stay connected and operate well during the faults. Compared with a series dynamic braking resistor (SDBR), two aspects are improved. First, a two-level control strategy and DC inductor circuit are used to ensure that the OCV-PD can limit the current impulse to protect DFIG system during an overcurrent fault. Second, the OCV-PD can protect system from overvoltage fault which a SDBR cannot do. Simulation results verify its validity and feasibility, finding that for overcurrent protection the OCV-PD outperforms a SDBR with an average decreased index of 3.29%, and for overvoltage protection it achieves an average index of 1.02%.
CITATION STYLE
Yan, S., Zhang, A., Zhang, H., Wang, J., & Cai, B. (2017). Transient stability enhancement of DC-connected DFIG and its converter system using fault protective device. Journal of Modern Power Systems and Clean Energy, 5(6), 887–896. https://doi.org/10.1007/s40565-017-0333-9