Abstract
The volatile and intermittent nature of distributed generators (DGs) in active distribution networks (ADNs) increases the uncertainty of operating states. The introduction of distribution phasor measurement units (D-PMUs) enhances the monitoring level. The trade-offs of computational performance and robustness of state estimation in monitoring the network states are of great significance for ADNs with D-PMUs and DGs. This paper proposes a second-order cone programming (SOCP) based robust state estimation (RSE) method considering multi-source measurements. Firstly, a linearized state estimation model related to the SOCP state variables is formulated. The phase angle measurements of D-PMUs are converted to equivalent power measurements. Then, a revised SOCP-based RSE method with the weighted least absolute value estimator is proposed to enhance the convergence and bad data identification. Multi-time slots of D-PMU measurements are utilized to improve the estimation accuracy of RSE. Finally, the effectiveness of the proposed method is illustrated in the modified IEEE 33-node and IEEE 123-node systems.
Author supplied keywords
Cite
CITATION STYLE
Liu, Z., Li, P., Wang, C., Yu, H., Ji, H., Xi, W., & Wu, J. (2023). Robust State Estimation of Active Distribution Networks with Multi-source Measurements. Journal of Modern Power Systems and Clean Energy, 11(5), 1540–1552. https://doi.org/10.35833/MPCE.2022.000200
Register to see more suggestions