Abstract
To perform analysis of the simultaneous faults of transmission lines is one of the challenging tasks. Most of thealgorithms fail to find the precise fault location under such conditions. An attempt is made in this study to analyse one of thesimultaneous faults called open conductor and ground fault. The essential objective of this study is to derive generalisedimpedance equations to identify precise fault location during simultaneous open conductor and ground fault that occurred on atransmission line with the help of its equivalent sequence components network. The proposed method has less complexity fordata processes unlike other methods such as advanced artificial intelligence, fuzzy logic, and neural networks. To validate theproposed method, simulations have been carried out using MATLAB/SIMULINK software on an existing different type of mediumtransmission line. Calculation results demonstrate the effectiveness of the derived equations claims around 95% accuracy toidentify fault location. The proposed scheme also works very efficiently during more than one simultaneous open conductor andground fault that occurred in the network. This study would be beneficial to the new researcher to analyse the behaviour of thenetwork during the simultaneous fault having a basic knowledge of the formation of a sequential network for different types offaults.
Cite
CITATION STYLE
Tailor, D. N., & Makwana, V. H. (2020). Analysis of faulted power system during simultaneous open conductor and ground fault. IET Generation, Transmission and Distribution, 14(22), 5319–5326. https://doi.org/10.1049/iet-gtd.2019.1211