Non-contact methods for high-voltage insulation equipment diagnosis during operation

17Citations
Citations of this article
12Readers
Mendeley users who have this article in their library.

Abstract

The article describes a complex of non-contact methods for remote diagnosis of high-voltage insulators as well as the two-channel method for remote diagnostics of the operating state of high-voltage insulators, based on the registration of partial discharges by electromagnetic and acoustic sensors. The presented device allows visual inspection and searches for faulty high-voltage equipment and a remote non-contact method of recording high-intensity electric fields of industrial frequency and their spatial distribution based on the electro-optical effect. The scheme of using the system for monitoring and diagnosing the technical condition of high-voltage support insulators of open switchgear is described. The results of experimental studies confirm the possibility of industrial applicability of the proposed method for non-contact remote diagnostics of the state of high-voltage insulators under operating voltage.

Cite

CITATION STYLE

APA

Ivanov, D. A., Sadykov, M. F., Yaroslavsky, D. A., Golenishchev-Kutuzov, A. V., & Galieva, T. G. (2021). Non-contact methods for high-voltage insulation equipment diagnosis during operation. Energies, 14(18). https://doi.org/10.3390/en14185670

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free