Due to the use of electrical current load that uses a lot of electronic components (passive non-linear electrical loads), so the impact will cause harmonics in the electrical network system. These harmonics can unwittingly cause a relatively large loss in electrical energy consumption and can lower the power factor of an electrical installation. Limits how much the harmonic distortion that is installed on the load adjusted to the IEEE 519-1992 standard. The study was conducted by taking data on a network of electrical installation of a building using measuring devices Fluke 43B Power Quality Analyser. The data is then processed and consulted with the standard IEEE 519-1992. Once the data has a discrepancy with the standard, further made the filter design using linear passive components. The design is then installed on the network installation by means of simulated order harmonic losses can be overcome so that the circuit meets the IEEE standard installation by changing the parameters of the linear load L and C. The results of this study indicate that THDi value decreased after the installation of filters for phase R fell by 9.39%, the S phase decreased by 7.54% and for the T phase decreased by 16.88%. So that meets the IEEE standard by 15%.