Abstract
This paper presents results of study of loss-of-excitation phenomena simulations. Loss of excitation is a very common fault in synchronous machine operating and can be caused by short circuit of the field winding, unexpected field breaker open or loss-of-excitation relay mal-operation. According to the statistic [1], the generator failure due to loss-of-excitation accounts for 69% of all generator failures. There has been concern over possible incorrect operation of the relay when operating the generator in the under-excited region, during stable transient swings and during major system disturbances. This article can serve as inputs for system operators in preparation of operation area or protection relaying area.
Cite
CITATION STYLE
Krištof, V., & Mešter, M. (2017). Loss of excitation of synchronous generator. Journal of Electrical Engineering, 68(1), 54–60. https://doi.org/10.1515/jee-2017-0007