Aiming at the problem of power coupling and complicated decoupling in the d-q coordinate system of a three-phase grid-connected inverter, a current closed-loop control strategy based on an improved QPIR (quasi-proportional integral resonant) controller in the a-b two-phase static coordinate system is proposed. Firstly, the mathematical model of an LCL three-phase grid-connected inverter is established, and its instantaneous power calculation equation is deduced. Secondly, the frequency method is applied to compare and analyze the proportional resonant, quasi-proportional resonant, and improved current controller, and the appropriate improved controller parameters are obtained according to the traditional proportional integral controller parameter design method and the weight coefficient. Finally, the improved controller is compared with the traditional controller in the simulation model of the LCL three-phase grid-connected inverter based on active damping. The results show that the proposed improved current control strategy has good dynamic response characteristics, can realize the non-static error control of grid-connected current, and realizes the decoupling control of active power and reactive power when the load jumps. At the same time, the results also prove the superiority of the proposed control strategy and verify its effectiveness.
CITATION STYLE
Li, Y., Zhang, J., Hao, Z., & Tian, P. (2021). Improved PR control strategy for an LCL three-phase grid-connected inverter based on active damping. Applied Sciences (Switzerland), 11(7). https://doi.org/10.3390/app11073170
Mendeley helps you to discover research relevant for your work.