Polyaluminium chloride dosing effects on coagulation performance: case study, barekese, ghana

28Citations
Citations of this article
161Readers
Mendeley users who have this article in their library.

Abstract

Alum, the predominant coagulant in conventional drinking water treatment schemes, has various disadvantages including the production of large volumes of sludge, lowering water pH (requiring pH adjustment using lime), limited coagulation pH range of 6.5 to 8.0, etc. At the Barekese Water Treatment Plant in Ghana, an alternative, the polyelectrolyte – polyaluminium chloride (PAC) is also used in coagulation but limited information is available on the operating conditions required to achieve better performance than alum-based coagulation. The aim of this study was to determine the optimal coagulant dose, mixing speed and operating pH for enhanced performance in water treatment. The effects on the treatment process of three different sets of mixing speed pairs – 180/40, 180/25 and 150/25 revolutions per minute (fast/slow) – in a pH range of 6.5 to 8.0 were investi-gated. The mixing speed and PAC dose yielding the best coagulation were 150/25 rpm and 15 mg/L respectively. The optimal pH range for PAC coagulation performance was 7.5 to 8.0.

Cite

CITATION STYLE

APA

Nti, S. O., Buamah, R., & Atebiya, J. (2021). Polyaluminium chloride dosing effects on coagulation performance: case study, barekese, ghana. Water Practice and Technology, 16(4), 1215–1223. https://doi.org/10.2166/wpt.2021.069