An intelligent sensor for the ultra-high-frequency partial discharge online monitoring of power transformers

23Citations
Citations of this article
17Readers
Mendeley users who have this article in their library.

Abstract

Ultra-high-frequency (UHF) partial discharge (PD) online monitoring is an effective way to inspect potential faults and insulation defects in power transformers. The construction of UHF PD online monitoring system is a challenge because of the high-frequency and wide-frequency band of the UHF PD signal. This paper presents a novel, intelligent sensor for UHF PD online monitoring based on a new method, namely a level scanning method. The intelligent sensor can directly acquire the statistical characteristic quantities and is characterized by low cost, few data to output and transmit, Ethernet functionality, and small size for easy installation. The prototype of an intelligent sensor was made. Actual UHF PD experiments with three typical artificial defect models of power transformers were carried out in a laboratory, and the waveform recording method and intelligent sensor proposed were simultaneously used for UHF PD measurement for comparison. The results show that the proposed intelligent sensor is qualified for the UHF PD online monitoring of power transformers. Additionally, three methods to improve the performance of intelligent sensors were proposed according to the principle of the level scanning method.

References Powered by Scopus

Review of condition assessment of power transformers in service

915Citations
N/AReaders
Get full text

Partial discharge monitoring for power transformers using UHF sensors part 1: Sensors and signal interpretation

421Citations
N/AReaders
Get full text

Partial discharge measurement in the ultra high frequency (UHF) range

245Citations
N/AReaders
Get full text

Cited by Powered by Scopus

Application of UHF sensors in power system equipment for partial discharge detection: A review

110Citations
N/AReaders
Get full text

Review of fiber optic diagnostic techniques for power transformers

54Citations
N/AReaders
Get full text

On-line partial discharge monitoring system for power transformers based on the simultaneous detection of high frequency, ultra-high frequency, and acoustic emission signals

33Citations
N/AReaders
Get full text

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Cite

CITATION STYLE

APA

Li, J., Li, X., Du, L., Cao, M., & Qian, G. (2016). An intelligent sensor for the ultra-high-frequency partial discharge online monitoring of power transformers. Energies, 9(5). https://doi.org/10.3390/en9050383

Readers' Seniority

Tooltip

PhD / Post grad / Masters / Doc 8

80%

Lecturer / Post doc 1

10%

Researcher 1

10%

Readers' Discipline

Tooltip

Engineering 14

100%

Save time finding and organizing research with Mendeley

Sign up for free