Abstract
In recent years, the use of R744 natural refrigerant has become increasingly popular in a wide range of applications from air conditioning to low-temperature refrigeration. This study focuses on optimizing the thermodynamic parameters of the R744/R134a cascade cycle operating under evaporative temperature varying from −23 °C to −29 °C, operating in tropical climates region. The parameters include the evaporating temperature, the condensing temperature, the subcooling temperature, and the superheating temperature in the low temperature cycle, and the evaporating temperature, the subcooling temperature, and the superheating temperature in the high temperature cycle. The study has given a rating of the influence of thermodynamic parameters on the coefficient of performance (COP) of the system. In addition, the study shows that the optimal dataset for all the above thermodynamic parameters is A3B3C2D1E1F3 with a COP of 2.560 in theory and 2.461 in experiment. Moreover, the ANOVA analysis method for the variances also shows the consistency of the above results with the highest error of 3.54% compared to the experiment.
Author supplied keywords
Cite
CITATION STYLE
Dang, T., Nguyen, H., & Dang, H. S. (2025). Thermal Parameters Optimization of the R744/R134a Cascade Refrigeration Cycle Using Taguchi and ANOVA Methods. Processes, 13(4). https://doi.org/10.3390/pr13041210