Sensor faults frequently occur in wastewater treatment plant (WWTP) operation, leading to incomplete monitoring or poor control of the plant. Reliable operation of the WWTP considerably depends on the aeration control system, which is essentially assisted by the dissolved oxygen (DO) sensor. Results on the detection of different DO sensor faults, such as bias, drift, wrong gain, loss of accuracy, fixed value, or complete failure, were investigated based on Principal Components Analysis (PCA). The PCA was considered together with two statistical approaches, i.e., the Hotelling’s T2 and the Squared Prediction Error (SPE). Data used in the study were generated using the previ-ously calibrated first-principle Activated Sludge Model no.1 for the Anaerobic-Anoxic-Oxic (A2 O) reactors configuration. The equation-based model was complemented with control loops for DO concentration control in the aerobic reactor and nitrates concentration control in the anoxic reactor. The PCA data-driven model was successfully used for the detection of the six investigated DO sensor faults. The statistical detection approaches were compared in terms of promptness, effectiveness, and accuracy. The obtained results revealed the way faults originating from DO sensor malfunction can be detected and the efficiency of the detection approaches for the automatically controlled WWTP.
CITATION STYLE
Luca, A. V., Simon-Várhelyi, M., Mihály, N. B., & Cristea, V. M. (2021). Data driven detection of different dissolved oxygen sensor faults for improving operation of the wwtp control system. Processes, 9(9). https://doi.org/10.3390/pr9091633