An islanding detection technique for inverter-based distributed generation in microgrids

41Citations
Citations of this article
49Readers
Mendeley users who have this article in their library.

Abstract

This article proposes a new passive islanding detection technique for inverter-based distributed generation (DG) in microgrids based on local synchrophasor measurements. The proposed method utilizes the voltage and current phasors measured at the DG connection point (point of connection, PoC). In this paper, the rate of change of voltages and the ratio of the voltage and current magnitudes (VoI index) at the PoC are monitored using micro-phasor measurement units. The developed local measurements based decentralized islanding detection technique is based on the VoI index in order to detect any kind of utility grid frequency fluctuations or oscillations and distinguishing them from islanding condition. The simulation studies confirm that the proposed scheme is accurate, robust, fast, and simple to implement for inverter-based DGs.

Cite

CITATION STYLE

APA

Karimi, M., Farshad, M., Hong, Q., Laaksonen, H., & Kauhaniemi, K. (2021). An islanding detection technique for inverter-based distributed generation in microgrids. Energies, 14(1). https://doi.org/10.3390/en14010130