Abstract
The aim of this experiment was to investigate convection heat transfer in the cooling processes of Al2O3-water nanofluid in concentrations of 0.15%, 0.25% and 0.5% by volume, respectively. The test section was a 1.25 m brass pipe with a 4.9 mm inner diameter and outer pipe of 38.5 mm diameter of a counter flow double-pipe heat exchanger. The temperatures at the nanofluid inlet in the inner pipe were a constant 40°C, and 23°C for the water at the inlet of the outer pipe. The results of this study indicated a more enhanced coefficient convective heat transfer of the cooling process than that of the heating process. The new equation of the Nusselt number obtained in the cooling process was Nunf=0.75Re0.846 Pr-2.28 φ0.03 at particle volume concentrations of 0.15%, 0.25% and 0.5%. The maximum ratio enhancement of the nanofluid heat transfer in the cooling process was 45.2% at a particle volume concentration of 0.25%, while for the heating process nanofluid heat transfer was same as that for distilled water.
Author supplied keywords
Cite
CITATION STYLE
Sudarmadji, S. (2015). The new correlations for heat transfer in the cooling process of Al2O3 - Water nanofluids in pipe. Journal of Applied Engineering Science, 13(4), 235–240. https://doi.org/10.5937/jaes13-8445