Numerical studies on smoke spread in the cavity of a double-skin façade

13Citations
Citations of this article
27Readers
Mendeley users who have this article in their library.

Abstract

In this paper, influence of two key factors, fire room height and outer pane tilt angle, on smoke spread in the cavity of a double-skin façade (DSF) was studied numerically. The fire room was located adjacent to the DSF on the 2nd, 4th and 6th floors, respectively. The outer pane tilt angle varied at 80°, 90° and 100°. All cases were under two fire heat release rates of 1 MW and 5 MW. Results suggested that fire room height and outer pane tilt angle had significant effects on smoke spread in the cavity. For different fire room heights, there were two markedly different scenarios of smoke spread in the cavity between two vertical panes in a high-rise building. For outer pane tilt angle, the DSF with an inward tilted or vertical outer pane was dangerous for the upper floors due to hot smoke adhering to the upper inner pane. However, the turbulent vortex in the DSF with an outward tilted outer pane prevented hot smoke flowing out from the fire room.

Cite

CITATION STYLE

APA

Ji, J., Li, Y. F., Shi, W. X., & Sun, J. H. (2016). Numerical studies on smoke spread in the cavity of a double-skin façade. Journal of Civil Engineering and Management, 22(4), 470–479. https://doi.org/10.3846/13923730.2014.897992

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free