Cascade control strategy for external carbon dosage in predenitrifying process

36Citations
Citations of this article
17Readers
Mendeley users who have this article in their library.
Get full text

Abstract

We propose a cascade control strategy composed of two Proportional-Integral (PI) controllers to regulate the nitrate concentration in the predenitrifying process by manipulating the external carbon dosage. It controls the nitrate concentrations in the effluent as well as in the final anoxic reactor simultaneously to strictly satisfy the quality of the effluent as well as to remove the effects of disturbances more quickly. The design of two PI controllers in the cascade control loop can be completed with the Ziegler-Nichols (Z-N) tuning rule together with a simple relay feedback identification method. Results from the Benchmark simulation confirm that both good set point tracking and satisfactory disturbance rejection can be guaranteed due to the structural advantages of the proposed cascade control strategy. Also, compared with a previous work, the fluctuation of the nitrate concentration in the effluent has been decreased significantly.

Cite

CITATION STYLE

APA

Cho, J. H., Sung, S. W., & Lee, I. B. (2002). Cascade control strategy for external carbon dosage in predenitrifying process. In Water Science and Technology (Vol. 45, pp. 53–60). IWA Publishing. https://doi.org/10.2166/wst.2002.0550