Reducing the Effect of Lightning on Step and Touch Voltages in a Grounding Grid Using a Nature-Inspired Genetic Algorithm with ATP-EMTP

9Citations
Citations of this article
35Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

This paper discusses the step and touch voltages, based on body resistance, in a grounding grid after a lightning strike at a 434-/21-kV substation. To ensure grounding grid safety, the maximum step and touch voltage should not exceed the safety criteria defined by the IEEE Std. 80. In this paper, ATP-EMTP and a genetic algorithm are used to analyze and optimize the step and touch voltages in a power grid. The voltages are calculated under normal conditions of a lightning strike at a power system. Thevenin's theorem is applied to calculate the step and touch voltages. The genetic algorithm is applied in ATP-EMTP to obtain the minimum level of step and touch voltages in the grounding grid after lightning strikes the power system. The step and touch voltages at different positions of the grounding grid are explained in this paper using the ATP-EMTP and the genetic algorithm. The computer simulation shows that the proposed scheme is highly feasible and technically attractive.

Cite

CITATION STYLE

APA

Farkoush, S. G., Wadood, A., Khurshaid, T., Kim, C. H., Irfan, M., & Rhee, S. B. (2019). Reducing the Effect of Lightning on Step and Touch Voltages in a Grounding Grid Using a Nature-Inspired Genetic Algorithm with ATP-EMTP. IEEE Access, 7, 81903–81910. https://doi.org/10.1109/ACCESS.2019.2923656

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free