Comparison Evaluations of VRF and RTU Systems Performance on Flexible Research Platform

9Citations
Citations of this article
20Readers
Mendeley users who have this article in their library.

This article is free to access.

Abstract

The energy performance of a variable refrigerant flow (VRF) system was evaluated using an occupancy-emulated research building in the southeastern region of the United States. Full- and part-load performance of the VRF system in heating and cooling seasons was compared with a conventional rooftop unit (RTU) variable-air-volume system with electric resistance heating. During both the heating and cooling seasons, full- and part-load conditions (i.e., 100%, 75%, and 50% thermal loads) were maintained alternately for 2 to 3 days each, and the energy use, thermal conditions, and coefficient of performance (COP) for the RTU and VRF system were measured. During the cooling season, the VRF system had an average COP of 4.2, 3.9, and 3.7 compared with 3.1, 3.0, and 2.5 for the RTU system under 100%, 75%, and 50% load conditions and resulted in estimated energy savings of 30%, 37%, and 47%, respectively. During the heating season, the VRF system had an average COP ranging from 1.2 to 2.0, substantially higher than the COPs of the RTU system, and resulted in estimated energy savings of 51%, 47%, and 27% under the three load conditions, respectively.

Cite

CITATION STYLE

APA

Lee, J. H., Im, P., Munk, J. D., Malhotra, M., Kim, M. S., & Song, Y. H. (2018). Comparison Evaluations of VRF and RTU Systems Performance on Flexible Research Platform. Advances in Civil Engineering, 2018. https://doi.org/10.1155/2018/7867128

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Save time finding and organizing research with Mendeley

Sign up for free