Abstract
Since the transmission distance of submarine cable transmission is inversely proportional to the input frequency, to solve the problem of large losses in the transmission process of offshore wind power, this paper proposes a three-frequency transformer which enables the output of 50 Hz at the input of 50/3 Hz excitation. In this paper, the magnetic flux of a three-dimensional wound core transformer is analytically modeled, the existing condition of magnetic flux harmonics of a threedimensional wound core transformer is analyzed, the distribution of harmonic content in magnetic flux is obtained, and the principle of realizing frequency conversion is expounded. Secondly, the finite element analysis of the frequency converter is carried out. Finally, a prototype of a frequency transformer is made and tested to verify the correctness of the proposed scheme.
Author supplied keywords
Cite
CITATION STYLE
Su, Z., Luo, L., Liu, J., Li, Z., Luo, H., & Zhao, P. (2022). Study of the Harmonic Analysis and Energy Transmission Mechanism of the Frequency Conversion Transformer. Energies, 15(2). https://doi.org/10.3390/en15020519
Register to see more suggestions