Partial Discharge Characteristics of C3F7CN Gas Mixture Using the UHF Method

4Citations
Citations of this article
6Readers
Mendeley users who have this article in their library.

Abstract

Manufacturing or assembly defects in gas-insulated equipment can introduce field enhancements that could lead to partial discharge (PD). This paper examines the PD characteristics of SF6 alternatives considered for potential application to retro-filling existing SF6-designed equipment. The PD performance of the C3F7CN/CO2 gas mixture and SF6 were characterised adopting the ultra-high frequency (UHF) method and investigated for different defect configurations, pressures, and gas mediums. Hemispherical rod-plane and plane-to-plane configurations with needle on the high-voltage (HV) and ground electrodes were used to mimic conductor and enclosure protrusion defects, respectively. The results demonstrate that with a needle length of 15 mm, the 20% C3F7CN/80% CO2 gas mixture had almost half the partial discharge inception and extinction voltages (PDIV/EV) of SF6. For less divergent fields, the 20% C3F7CN/80% CO2 gas mixture demonstrated a comparable PDIV/EV performance as SF6. The phase-resolved PD patterns of the 20% C3F7CN/80% CO2 gas mixture demonstrated a 3-stage transition phase that was not observed with SF6, which could be due to the discharge mechanism of the weakly attaching CO2 gas used within the mixture.

References Powered by Scopus

Green Gas to Replace SF6 in Electrical Grids

421Citations
N/AReaders
Get full text

Partial Discharge Diagnostics for Gas Insulated Substations

223Citations
N/AReaders
Get full text

High Voltage and Electrical Insulation Engineering

204Citations
N/AReaders
Get full text

Cited by Powered by Scopus

Analysis of Breaking Characteristics of C<inf>4</inf>F<inf>7</inf>N/CO<inf>2</inf> Mixture Gas in Circuit Breaker

3Citations
N/AReaders
Get full text

Characteristics Analysis and Domain-Adaptive Recognition Methodology of Partial Discharge for C<inf>4</inf>F<inf>7</inf>N/CO<inf>2</inf> Eco-Friendly GIS

1Citations
N/AReaders
Get full text

Research on the Interruption Performance of Environmentally Friendly 126 kV Circuit Breaker

0Citations
N/AReaders
Get full text

Register to see more suggestions

Mendeley helps you to discover research relevant for your work.

Already have an account?

Cite

CITATION STYLE

APA

Loizou, L., Han, Q., Chen, L., Liu, Q., Waldron, M., Wilson, G., … Seltzer-Grant, M. (2022). Partial Discharge Characteristics of C3F7CN Gas Mixture Using the UHF Method. Energies, 15(20). https://doi.org/10.3390/en15207731

Readers over time

‘22‘23‘2502468

Readers' Discipline

Tooltip

Engineering 4

100%

Article Metrics

Tooltip
Mentions
Blog Mentions: 1

Save time finding and organizing research with Mendeley

Sign up for free
0