Analysis and handling methods of two protection action events in HVDC transmission systems

7Citations
Citations of this article
N/AReaders
Mendeley users who have this article in their library.
Get full text

Abstract

Over-high neutral bus voltage will affect the normal operation of a high voltage direct current (HVDC) transmission system, especially when the system is in monopolar operation condition. This paper describes an event of ground return transfer switch protection action caused by induction voltage when one of the double-circuit DC transmission systems is in monopolar operation condition and an event of converter differential protection action caused by commutation failure. To avoid recurrence of similar accidents, an overall analysis is made on the protection action process of two events and improving measures are put forward. Validity of the improving measures is proved by the test and actual operations.

Cite

CITATION STYLE

APA

Yao, Q., & Li, H. (2016). Analysis and handling methods of two protection action events in HVDC transmission systems. Dianli Xitong Zidonghua/Automation of Electric Power Systems, 40(23), 163–167. https://doi.org/10.7500/AEPS20160123001