The performance of an advanced three-bed adsorption chiller with a mass recovery cycle has been experimentally investigated in the present study. The temperature and pressure of various components of the chiller were monitored to observe the dynamic behaviour of the chiller. The performances in terms of the coefficient of performance (COP) and specific cooling power (SCP) were compared with a conventional single stage. The results show that the proposed cycle produces COP and SCP values superior to those of the conventional single stage cycle for heat source temperature below 75 °C.
Author supplied keywords
Cite
CITATION STYLE
Uyun, A. S., Miyazaki, T., Ueda, Y., & Akisawa, A. (2009). Experimental investigation of a three-bed adsorption refrigeration chiller employing an advanced mass recovery cycle. Energies, 2(3), 531–544. https://doi.org/10.3390/en20300531