Abstract
This study experimentally evaluates an innovative double counter-flow dew-point evaporative cooler with efficient wet-channel materials for residential building cooling. Tested under varying conditions in a double enthalpy-difference laboratory, the system achieves 118% wet-bulb effectiveness and 83% dew-point effectiveness at a 1:1 secondary/primary air ratio (dry-bulb temperature of 38°C and wet-bulb temperature of 23°C), delivering 3.31 kW cooling capacity. Compared to other existing systems, wet-bulb and dew-point effectiveness improve by 11.74% and 10.67%, respectively. The coefficient of performance (i.e. COP) reaches 10–13.2 in dry regions and 8.4 in humid climates, demonstrating superior energy efficiency for sustainable air conditioning. The new dew-point indirect evaporative cooler adopts a new structural design, wet material, and intermittent water supply scheme, which significantly improves the wet-bulb effectiveness, dew-point effectiveness, and COP compared with existing air coolers of the same type, and provides new ideas for material and structural innovations in subsequent research.
Author supplied keywords
Cite
CITATION STYLE
Huang, X., Zhao, Y., Chu, J., Jiang, S., Deng, G., Lyu, W., & Wu, M. (2025). Experimental study of an innovative counter-flow dew-point indirect evaporative cooler with polymer composite membrane. International Journal of Low-Carbon Technologies, 20, 1901–1912. https://doi.org/10.1093/ijlct/ctaf122