Impact of Air Gap Defects on the Electrical and Mechanical Properties of a 320 kV Direct Current Gas Insulated Transmission Line Spacer

6Citations
Citations of this article
6Readers
Mendeley users who have this article in their library.

Abstract

Air gap defects inside a spacer reduce its insulation performance, resulting in stress concentration, partial discharge, and even flashover. If such gap defects are located at the interface between the insulation and conductor, a decrease in mechanical stress may occur. In this work, a finite element method-based simulation model is developed to analyze the influence of gap defects on the electrical and mechanical properties of a ±320 kV direct current gas insulated line (DC GIL) spacer. Present findings reveal that a radially distributed air gap produces a more significant effect on the electric field distribution, and an electric field strength 1.7 times greater than that of the maximum surface value is observed at the air gap. The axial distribution dominates the distortion of the surface stress by generating a stress concentration region in which the maximum stress of the air gap is twice the pressure in the surrounding area.

Cite

CITATION STYLE

APA

Deng, Y., Fan, X., Luo, H., Wang, Y., Wu, K., Liang, F., & Li, C. (2023). Impact of Air Gap Defects on the Electrical and Mechanical Properties of a 320 kV Direct Current Gas Insulated Transmission Line Spacer. Energies, 16(10). https://doi.org/10.3390/en16104006