Abstract
This paper present a review of mathematical procedures for heat transfer studies in cross flow through finned tube pack. Is given a new model for heat transfer calculations during airflow through finned tubes bank in air cooled condenser systems (ACC). The model was correlated with a total of 783 sets of available experimental data provided by ten authors of recognized prestige in the research area. The air flow bathes a package of finned tubes with an inclination of 45° to 60° with respect to the horizontal line. The studies were performed for ST/SL intervals between 0.4 and 2, air flow velocity of 0.1 to 100 m/s, an ambient temperature of 15 to 43°C, the incident wind velocity over the installation between 0 and 45 km/h, the outer equivalent diameter of the bare tubes between 0.019 and 0.05 m, a fins height between 2.7 and 7.9 mm.The fins thicknesses ranging between 1.3 and 3.5 mm and a number of fins per unit tube length between 315 and 394. The mean deviation found was 6.9% in 85.3% of the correlated experimental data.
Author supplied keywords
Cite
CITATION STYLE
Camaraza-Medina, Y., Rubio-Gonzales, Á. M., Cruz-Fonticiella, O. M., García-Morales, O. F., Vizcón-Toledo, R., & Quiza-Sardiñas, R. (2018). Simplified analysis of heat transfer through a finned tube bundle in air cooled condenser-second assessment. Mathematical Modelling of Engineering Problems, 5(4), 365–372. https://doi.org/10.18280/mmep.050413