This paper investigates the air pollutions in space ventilated in two High School classrooms. The analysis consists of comparison of one classroom with hybrid ventilation system and another one stander-by classroom with natural ventilation. Several studies regarding indoor air quality during the experimental campaign have been done for VOC, CO2, CO, other pollutants, keeping monitored for humidity and temperature. The experimental demonstrated that the highest value for CO2 in stander-by classroom is 2691 ppm and in classroom with hybrid ventilation is 1897 ppm, while values for CO are 1.1 / 1.1 ppm and VOC 0.14 / 0.06 ppm, better use hybrid ventilation.
Cite
CITATION STYLE
Vasile, V., DIma, A., Zorila, E., Istrate, A., & Catalina, T. (2018). Comparison of indoor air pollutants concentration in two Romanian classrooms. In E3S Web of Conferences (Vol. 32). EDP Sciences. https://doi.org/10.1051/e3sconf/20183201023