Abstract
Absorption chillers operate well below their reversible or endoreversible limits because their thermodynamic behavior is dominated by internal dissipation, a significant part of which occurs in the chiller's heat exchangers. This fact has summarily been omitted from earlier analyses. It translates into incorrect values for the refrigerant process-average temperature (PAT), and leads to noticeable errors in chiller diagnostics and optimization. Using experimental measurements from an absorption chiller, in concert with a computer simulation code and an analytic thermodynamic model, we fortify these claims with quantitative examples. The correct PAT is derived and its significance in chiller analysis is high-lighted. Aspects of chiller optimization that are unique to absorption technology, as opposed to conventional vapor-cycle reciprocating chillers, are also illustrated. We also substantiate that commercial absorption chiller technology has empirically evolved to close to optimal operating conditions. © 1998 Elsevier Science Ltd. All rights reserved.
Author supplied keywords
Cite
CITATION STYLE
Ng, K. C., Tu, K., Chua, H. T., Gordon, J. M., Kashiwagi, T., Akisawa, A., & Saha, B. B. (1998). Thermodynamic analysis of absorption chillers: Internal dissipation and process average temperature. Applied Thermal Engineering, 18(8), 671–682. https://doi.org/10.1016/S1359-4311(97)00119-1