Airborne infection in a fully air-conditioned hospital: I. Air transfer between rooms

14Citations
Citations of this article
14Readers
Mendeley users who have this article in their library.

Abstract

Measurements have been made of the extent of air exchange between patient rooms in a fully air-conditioned hospital using a tracer-gas method. When the rooms were ventilated at about six air changes per hour, had an excess airflow through the doorway of about 0.1 m.3/sec. and the temperature difference between rooms and corridor was less than 0.5° C., concentrations of the tracer in rooms close to that in which it was being liberated were 1000-fold less than that in the source room. This ratio fell to about 200-fold in the absence of any excess airflow through the doorways. Considerable dilution took place along the corridors so that the concentration fell by around 10-fold for every 10 m. of corridor. © 1975, Cambridge University Press. All rights reserved.