Impedance-model-based SSR analysis for type 3 wind generator and series-compensated network

404Citations
Citations of this article
102Readers
Mendeley users who have this article in their library.

Your institution provides access to this article.

Abstract

Interaction between doubly fed induction generator (DFIG) Type 3 wind generators and series-compensated networks can lead to subsynchronous resonance (SSR) oscillationsa phenomenon observed in the real world. In this paper, impedance-based Nyquist stability criterion is applied to analyze the SSR phenomena. Impedance models of a DFIG along with its rotor-side converter (RSC) and grid-side converter, and a series-compensated network are derived in terms of space vectors. The DFIG impedance and the network impedance are analyzed to show the impact of wind speed, compensation level, and RSC current controller gain on SSR stability. Nyquist maps are also used to demonstrate the impact on SSR stability. Simulation studies are carried out to show SSR controller interaction. This paper successfully demonstrates that the interaction between the electric network and the converter controller is a leading cause of the SSR phenomena recently observed in wind generation grid integration. © 1986-2012 IEEE.

Cite

CITATION STYLE

APA

Miao, Z. (2012). Impedance-model-based SSR analysis for type 3 wind generator and series-compensated network. IEEE Transactions on Energy Conversion, 27(4), 984–991. https://doi.org/10.1109/TEC.2012.2211019